Добро пожаловать на Must Power.

EH5000 Series High Frequency Online UPS (10-20KVA)

High Frequency Online UPS

EH5000 Series (10-20KVA)

This Online Series is an uninterruptible power supply incorporating conversion technology. It provides perfect protection specifically for computer equipment, communication systems to computerized instruments.The double-conversion principle eliminates all mains power disturbances. A rectifier converts the alternating current from the utility power to direct current. This direct current charges the batteries and powers the inverter. On the basis of this DC voltage. the inverter generates a sinusoidal AC voltage which is constantly powering the loads.Computers and Peripherals are thus powered entirely by the UPS. In the event of power failure, the maintenance-free batteries power the inverter.

192VDC
Напряжение батареи

8KW
Capacity

12KW
Capacity

16KW
Capacity

Где купить?

Downloads: EH5000 Series (10-20KVA).pdf

Обзор

eh5000-1

LCD / LED информационный дисплей

1. Inverter Output
2. Standby
3. Fault
4. LCD Screen
5. On/mute
6. Select
7. Off/enter


LCD / LED информационный дисплей

1. FAULT INFO
2. LINE INFO
3. BATTERY INFO
4-8. Load/battery capacity info
9. Bypass info
10. INVERTER INFO

eh5000-2


eh5000-3

Рисунок 1 Информация о задней панелью

1. RS232
2. Breaker
3. AC Input Socket
4. Intelligent Interface
5. AC Output Socket
6. Surge Protect Socket


  • IGBT technoligy;
  • N+X parallel redundancy;
  • LCD/LED optional;
  • Smart RS232 port for computer monitoring;
  • Cold start directly.

Specification

Model  3HC10KS  3HC15KS  3HC20KS 
Capacity(VA/W) 10KVA/8KW  15KVA/12KW  20KVA/16KW 
INPUT
Phase 3PH 4W+G
Voltage Range 210 ~ 475VAC
Frequency 46~64Hz; 50~60Hz Autoadaptation
Power Factor >0.95
OUTPUT
Voltage Range 220/ 230/240* (1±1%) VAC
Frequency Range Main Mode: (46 ~ 54)Hz/(56 ~ 64)Hz; Battery Mode: 50 Hz(± 0.1%) Hz or 60 Hz(± 0.1%) Hz
Crest Ratio 3:1
Power Factor 0.8
Wave Form Pure Sine wave
Outlet Hard Wiring with Terminal Black
TRANSFER TIME
Transfer Time Zero
Inverter To Bypass Zero
INDICATOR
LED Panel Load/ Battery Capacity/ Main Mode/ Bypass Mode/ Fault
LCD Panel Load/ Battery/ Input/ Output/Operation Mode
ENVIRONMENT 
Operating Environment 0- 40°C
Humidity 20-90 % (non-condensing)
Noise Level < 60dB @ 1 Meter
Temperature -25°C – 55°C(no battery)
OTHER
Protection Load<105%, Keeping working; 105%1min; 125% 30sec
Efficiency Up to 90%
Battery Inbuilt External battery
Battery DC Voltage DC192V
PHYSICAL
Dimension W*H*D(mm) 248*500*616
Net Weight(kgs) 27 35 35
MANAGEMENT 
Smart RS-232/USB Supports Windows®98/2000/2003/XP/Vista/2008,Windows®7,Linux,and MAC
Optional SNMP Power management from SNMP manager and web browser
*required
*required
*required
*required